Fire Extinguisher Compliance: Selection, Placement and Servicing Under AS 2444 and AS 1851

Fire extinguishers are the most common fire safety equipment in any Australian workplace, and the ones most likely to be quietly non-compliant. Compliance is not simply having extinguishers on the wall. It is having the right type, in the right place, serviced on schedule, with records to prove it. Two Australian standards sit behind that: AS 2444 for selecting and locating extinguishers, and AS 1851 for servicing and maintaining them. Miss any part and the equipment may fail when it is needed, or fail an audit well before that.

This guide covers fire extinguisher compliance from a facility manager’s perspective: the right type, the right place, the right servicing, and who carries the duty. It is about keeping the equipment compliant. Building the skill to use one is a separate exercise, covered by hands-on fire extinguisher training, and our post on the evolution of fire extinguisher training explains how that training works.

What compliance actually means

Extinguisher compliance has three parts, and all three have to hold at once: selection, placement and servicing. An office can have plenty of extinguishers and still be non-compliant because they are the wrong type for the hazard, poorly placed, or overdue for service. The fourth element that ties it together is records, because compliance you cannot evidence is compliance you cannot prove.

Selection: the right type for the hazard (AS 2444)

AS 2444-2001, Portable fire extinguishers and fire blankets – Selection and location, requires extinguishers to be chosen for the fire risks actually present in each area. Australian fires are grouped into classes, and the extinguisher has to match: Class A (ordinary combustibles), Class B (flammable liquids), Class C (flammable gases), Class D (combustible metals), Class E (electrical) and Class F (cooking oils and fats).

In practice that means an ABE dry powder unit as the general workhorse for most areas, carbon dioxide for server rooms and switchboards where residue would damage electronics, and wet chemical plus a fire blanket in commercial kitchens for Class F oils. The most common selection failure is a single type used everywhere, which leaves some areas with an extinguisher that is useless, or dangerous, for the fire most likely to occur there.

Placement: the right place (AS 2444)

The second half of AS 2444 is location, because an extinguisher that cannot be reached quickly is no use. Extinguishers should sit along normal paths of travel and near identified hazards, be clearly signed, and be mounted so the handle is no higher than about 1200mm and the base no lower than about 100mm. Occupants should never have to move toward a fire to reach one, and for Class A risks without sprinklers the maximum travel distance to an extinguisher is 15 metres.

Placement should also match what is shown on your evacuation diagrams, so the signage, the diagrams and the equipment all tell occupants the same story.

Servicing: the right maintenance (AS 1851)

Selecting and placing extinguishers correctly is undone if they are not maintained. Servicing follows AS 1851-2012, Routine Service of Fire Protection Systems and Equipment, which sets a layered schedule for portable extinguishers:

  • Six-monthly: a routine inspection and test by a competent technician, checking pressure, condition, signage, access and the anti-tamper seal.
  • Annually: a more detailed service, including a closer look at the hose, nozzle and mounting.
  • Every five years: a major overhaul and hydrostatic pressure test, with many sites choosing to replace the unit at that point.

Every extinguisher must carry a maintenance tag recording the date and result of each service. Fire blankets follow the same six-monthly inspection. The practical compliance test is simple: if an extinguisher has no current tag, it is not demonstrably compliant, whatever its condition.

Who carries the duty

The duty to provide and maintain compliant fire equipment sits with the person conducting the business or undertaking, which in most workplaces means the building owner or the facility manager. Servicing is usually outsourced to a fire equipment contractor, and that is fine, but the duty itself cannot be outsourced. The organisation remains responsible for making sure the service happens on schedule and that the records are kept and available.

A note on lithium-ion batteries

One modern caution sits outside the standard extinguisher picture. A lithium-ion battery fire is not a routine extinguisher job and should not be treated as one. See our guide on lithium-ion battery fires for why those behave differently and call for earlier evacuation rather than first-attack firefighting.

Where an audit fits

The simplest way to know whether your extinguishers are compliant is to have them audited. An audit confirms the right types are present for each area, correctly placed and signed, charged, in date, and tagged, and it surfaces the gaps before an incident or an inspection does. Our audits and inspections service covers exactly this, as part of broader AS 3745 compliance.

Get your extinguishers compliant

Compliant fire extinguishers are a small, ongoing discipline: right type, right place, serviced on schedule, records kept. First 5 Minutes has helped Australian organisations get their fire safety right for more than 40 years. Explore our audits and inspections service, our AS 3745 compliance essentials, and our fire extinguisher training, or contact our team on 1300 321 120 to review the extinguishers at your workplace.

Frequently asked questions

Which standards cover fire extinguishers in Australia?

AS 2444-2001 covers selection and location, and AS 1851-2012 covers routine servicing and maintenance. Together they define what a compliant extinguisher setup looks like.

How often do fire extinguishers need servicing?

Under AS 1851, portable extinguishers need a six-monthly inspection and test, a more detailed annual service, and a hydrostatic pressure test (or replacement) every five years, all by a competent technician.

What is checked at the six-monthly service?

Pressure, physical condition, hose and nozzle, signage, accessibility, and the anti-tamper seal, with the result recorded on the extinguisher’s maintenance tag.

Who is responsible for extinguisher compliance?

The person conducting the business or undertaking, usually the building owner or facility manager. Servicing can be outsourced to a contractor, but the duty to keep equipment compliant cannot be.

How far should an extinguisher be from staff?

Under AS 2444, the maximum travel distance to a Class A extinguisher is 15 metres in areas without sprinklers, and extinguishers should sit along paths of travel and near hazards.

What type of extinguisher goes where?

Match the type to the hazard: ABE dry powder for general areas, carbon dioxide for electrical risks such as server rooms, and wet chemical with a fire blanket for commercial kitchens. A single type everywhere is a common non-compliance.

What records do we need to keep?

Each extinguisher must carry a maintenance tag showing the date and result of each service. Without a current tag, an extinguisher is not demonstrably compliant, whatever its condition.

Does staff training count as compliance?

No. Training builds the skill to use an extinguisher and is valuable, but it is separate from the equipment compliance set by AS 2444 and AS 1851. A compliant workplace needs both.